1SFC132003M0201

10:70 Start ramp, second sequence

Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Start Ramp2
This parameter makes it possible to set the start ramp time
for the second parameter set.
Parameter
Default value
text
Start
10 s
Ramp2

10:71 Initial voltage, second sequence

Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Init Volt2
This parameter makes it possible to set the initial voltage for
the second parameter set.
Parameter
Default value
text
Init Volt2
30%

10:72 Current limit, second sequence

Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Curr Lim2
This parameter makes it possible to set the current limit level
for the second parameter set.
Parameter
Default value Setting range
text
Curr Lim2
4 x I
e
Setting range
Description
1...30s, 1...120s Second
sequence, time
for start ramp
Setting range
Description
30...70%
Second
sequence, ini-
tial voltage for
start ramp
Description
2.0...7.0 x I
Second
e
sequence, cur-
rent limit
Chapter 10
Functions
169