Environmental Influence; Specifications - ABB PST30 Installation And Commissioning Manual

Softstarters
Hide thumbs Also See for PST30:
Table of Contents

Advertisement

Chapter 3
Description
26
3:6
3:7
Degree of protection
(Main circuit)
Operating position
Ambient temperature
Altitude
Pollution degree
Relative humidity
Standards
Standards UL
PTC input
Marine approvals

Environmental influence

The product is designed to minimize the environmental
affects during manufacturing and use of the product. Most of
the materials used, are of recycle type and shall be handled
and recycled according to existing laws.
Further information regarding used material and recycling of
the product can be found at:
www.abb.com/lowvoltage

Specifications

IP 10 for PST30...72
IP 00 for PST85...1050
±
°
Vertical at
10
°
Storage: -25
C to +70
°
Operation: 0
C to +40
without derating
°
+40
C to +50
with derating 0.8% / °C (0.8%/ 33.8°F)
1000 m (3281 ft.) above sea level without derating
1000 - 4000 m (3281 - 13123 ft.) with derating 0.007% /m
3
5 - 95% (non condensing)
IEC 60947-1
IEC 60947-4-2
EN 60947-1
EN 60947-4-2
UL508
IEC 60947-8 Mark A detectors
DIN 44081 and DIN 44082
Contact your ABB sales office
°
°
°
C (-13
F to 158
F)
°
°
°
C (32
F to 104
F
°
°
°
C (104
F to 122
F)
1SFC132003M0201