ABB PST30 Installation And Commissioning Manual page 97

Softstarters
Hide thumbs Also See for PST30:
Table of Contents

Advertisement

1SFC132003M0201
Locked rotor protection (Locked Rotor)
Activate the protection if required by changing to Yes.
If "Yes" is selected, the following settings will be
available:
Locked rotor level (Lock R Lev)
Set the level of the locked rotor protection.
Available only if the protection is selected.
Locked rotor time (Lock R Time)
Set the time for the locked rotor protection.
Available only if the protection is selected.
Locked rotor type of operation (Lock R Op)
Select what operation shall be asserted if the locked rotor
protection is activated:
Stop–M
The motor will stop and a manual reset is
required.
Stop–A
The motor will stop and automatic reset is
performed.
Ind
Only indication will be given.
Press Store to save the selected operation.
Chapter 7
Settings and configuration
97