Chapter 10
Functions
Figure 12: Kick start
138
10:12 Kick start
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Kick Start
In some applications it can be necessary to kick loose the
motor i.e. initial friction, and therefore a kick start can be
used. With this function a selectable fix voltage is applied
during a settable time. Note that the current limit function is
not working during kick start.
Parameter
Default value
text
Kick Start
No
10:13 Kick start level
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Kick Level
With this parameter it is possible to set the level of the kick
start. It is active only if kick start is selected.
Parameter
Default value
text
Kick Level
50%
10:14 Kick start time
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Kick Time
This parameter makes it possible to set the time of the kick
start. It is active only if kick start is selected.
Parameter
Default value Setting range
text
Kick Time
0.2 s
Setting range
Description
Yes, No
Selection of Kick
Start
Setting range
Description
50...100%
Level of Kick
Start
Description
0.1...1.5 s
Time for Kick Start
1SFC132003M0201