ABB rec670 Commissioning Manual page 181

Intelligent electronic device
Hide thumbs Also See for rec670:
Table of Contents

Advertisement

1MRK 511 360-UEN A
Bay control REC670 2.1 IEC
Commissioning manual
Testing functionality by secondary injection
No ECHO and CS should appear.
4.
Abruptly reverse the current to the setting of AngleRCA setup lagging the
voltage, to operate the forward directional element.
No ECHO and CS should appear.
5.
Switch off the current and check that the ECHO and CS appear on the
corresponding binary output during 200ms after resetting the directional
element.
6.
Switch off the CRL binary input.
7.
Activate the BLOCK binary input.
8.
Activate the CRL binary input.
No ECHO and CS should appear.
9.
Switch off the polarizing voltage and reset the BLOCK and CRL binary input.
WEI = Echo & Trip
If setting
1.
Inject the polarizing voltage 3U0 to about 90% of the setting (3U0>) operating
voltage.
2.
Activate the CRL binary input.
No ECHO, CS and TRWEI outputs should appear.
3.
Increase the injected voltage to about 110% of the setting (3U0) operating
voltage.
4.
Activate the CRL binary input.
5.
Check that the ECHO, CS and TRWEI appear on the corresponding binary
output or on the local HMI.
6.
Reset the CRL binary input.
7.
Activate the BLOCK binary input.
8.
Activate the CRL binary input.
No ECHO, CS and TRWEI outputs should appear.
9.
Reset the CRL and BLOCK binary input.
Section 10
175

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 seriesRelion rec670

Table of Contents