Accessories; Tzidc-120; Communication - ABB TZIDC Operating Instructions Manual

Electro-pneumatic positioner
Table of Contents

Advertisement

Direction of action (logical state)
Proximity switch
< Lim. 1
SJ2-SN (NC)
0
SJ2-S1N (NO)
1
IMPORTANT (NOTE)
When using SJ2_S1N (NO), the TZIDC positioner may only
be used at an ambient temperature range from -25 ... 85 °C
(-13 ... 185 °F).
Digital position feedback with 24 V microswitches
Two microswitches for independent position signaling. Switching
points adjustable between 0 ... 100 %.
Voltage
Load rating
Contact surface
Mechanical position indicator
Indicator disk in enclosure cover, linked with positioner feedback shaft.
IMPORTANT (NOTE)
These options are also available for retrofitting by Service.
1)
The proximity switches or 24 V microswitches for digital feedback
are activated directly via the positioner axis and can only be
used in combination with the optionally available mechanical
position indicator.

9.2.10 Accessories

Mounting material
-
Attachment kit for linear actuators to DIN/IEC 534 / NAMUR
-
Attachment kit for rotary actuators to VDI / VDE 3845
-
Attachment kit for integral mounting to control valves
-
Attachment kit for actuator-specific attachment upon request
Pressure gauge block
-
With pressure gauges for supply and output pressure.
-
Pressure gauges with housing ø 28 mm (1.1 inch), with
connection block in aluminum, black
-
Installation material for mounting on positioner
Filter regulator
All metal version in brass, varnished black, bronze filter element
(40 µm) and condensate drain.
Max. pre-pressure 16 bar (232.06 psi), output adjustable to
1.4 ... 6 bar (20 ... 90 psi)
PC software for configuration and operation
DSV401 (SMART VISION) with DTM available on CD-ROM
42/18-84-EN
Position
> Lim. 1
< Lim. 2
> Lim. 2
1
1
0
0
0
1
1)
max. 24 V AC / DC
max. 2 A
10 µm Gold (AU)
TZIDC, TZIDC-110, TZIDC-120
9.3

TZIDC-120

9.3.1

Communication

Specification
Physical Layer
Transmission rate
Block types
Block class
Number of linkage objects
Device description (DD)
File
Max. execution time
Supply voltage
Max. permissible voltage
Power consumption
Current in the event of an
error
FF Certification
Device name
Dev. ID
Device address
ATEX certificate for FISCO
Insensitive to reversed
polarity
Class
Factory default
Diagnostic functions
Specifications
FOUNDATION Fieldbus, version 1.5
Model 113, 121 (IEC 61158-2)
31.25 Kbit/s
1 AO Function block
1 PID block
1 Resource block
1 Transducer block
1 physical block
AO block: standard
PID block: enhanced
Resource block: enhanced
Transducer block: custom
22
Rev. No. 1 (file name 0201.ffo,
0201.sym)
Common file format (file name:
020101.cff)
AO block: 40 milliseconds
PID block: 50 milliseconds
Power feed from the fieldbus
9.0 ... c 32.0 V DC
35 V DC
11.5 mA
15 mA (11.5 mA + 3.5 mA)
Registered with ITK 4.51, Dec.2003
IT Camp. Number IT023200
ABB TZIDC, TZIDC-110, TZIDC-
120-TAG
0003200028-TZIDC, TZIDC-110,
TZIDC-120XXXXXXXXXX
Between 10 and 247, default
address 23
Yes
Yes
LM profile 32L, 31 PS
The positioner is not delivered in an
aligned state. To adjust the
operating range and control
parameters, an automatic
configuration must be run on the
unit. Otherwise, the transducer block
remains in out-of-service mode.
Self-diagnostics for the positioner
hardware and software, valve
diagnostics with enhanced alarm
handling