Housing; Options; Accessories - ABB TZIDC Operating Instructions Manual

Electro-pneumatic positioner
Table of Contents

Advertisement

9.3.8

Housing

Material / Degree of protection
Aluminum, protection class IP 65 (optional IP 66) / NEMA 4X
Surface / Color
Electrostatic dipping varnish with epoxy resin, stove-hardened.
Case varnished black, RAL 9005, matte, housing cover Pantone
420.
Electrical connections
Screw terminals:
Max. 1.0 mm
Max. 2.5 mm
IMPORTANT (NOTE)
Do not expose the terminals to strain.
Four thread combinations for cable entry and pneumatic
connection
- Cable: thread 1/2-14NPT, air pipe: thread 1/4-18 NPT
- Cable: thread M20 x 1,5, air pipe: thread 1/4-18 NPT
- Cable: thread M20 x 1,5, air pipe: thread G 1/4
- Cable: thread G 1/2, air pipe: thread Rc 1/4
(Optional: With cable gland(s) and pipe plugs if necessary)
Weight
1,7 kg (3,75 lb)
Mounting orientation
Any
9.3.9

Options

Module for the emergency shutdown function
Supply voltage
Safe position is activated when
Explosion protection
A separate 24 V DC signal is normally applied to the emergency
shutdown module, which connects through the signal from the
microprocessor to the I/P module.
When the 24 V DC signal is interrupted, the pneumatic module
executes the respective safety function, depending on the mechanical
construction:
The positioner output Y1 is depressurized, and the valve is moved to
the safe position. In case of a double-acting actuator the second
output Y2 is additionally pressurized.
IMPORTANT (NOTE)
The emergency shutdown module can only be used with
pneumatics with the safe position "fail-safe".
The emergency shutdown module works independently of the mother
board, i.e. all information from the final control element is available in
the supervisory process control system at any time.
Mechanical position indicator
-
Indicator disk
-
Cover with transparent dome
-
Symbol label
-
Extension shaft
42/18-84-EN
2
(AWG 17) for options
2
(14 AWG) for bus connector
24 V DC (20 ... 30 V DC)
(galvanically isolated from input
signal)
voltage < 5 V
see certificate (operating
instructions)
TZIDC, TZIDC-110, TZIDC-120
Digital position feedback with proximity switches
Two proximity switches for independent position signaling. Switching
points adjustable between 0 ... 100 %
Current circuits acc. to DIN 19234 / NAMUR
Supply voltage
Signal current < 1.0 mA
Signal current > 2.0 mA
(function dependent on software and electronics for actuator)
Direction of action (logical state)
Proximity switch
< Lim. 1
SJ2-SN (NC)
0
SJ2-S1N (NO)
1
Digital position feedback with 24 V microswitches
Two microswitches for independent position signaling. Switching
points adjustable between 0 ... 100 %.
Voltage
Load rating
Contact surface
Mechanical position indicator
Indicator disk in enclosure cover, linked with positioner feedback
shaft.
*
The "digital feedback" is activated directly from the axis of rotation for
the variable pick-off and can only be used with the "mechanical
position indicator".
IMPORTANT (NOTE)
These options are also available for retrofitting by Service.

9.3.10 Accessories

Mounting material
-
Attachment kit for linear actuators to DIN/IEC 534 / NAMUR
-
Attachment kit for rotary actuators to VDI/VDE 3845
-
Attachment kit for integral mounting to control valves
-
Attachment kit for actuator-specific attachment upon request
Pressure gauge block
-
Pressure gauges for supply and output pressure
-
Pressure gauges with housing ø 28 mm
-
Aluminum connection block in black
-
Installation material for mounting on positioner
Filter regulator
All metal version in brass, varnished black, bronze filter element
(40 µm) and condensate drain.
Max. pre-pressure 16 bar (232 psi), output adjustable to 1.4 ... 6 bar
(20.31 ... 90 psi)
Specifications
5 ... 11 V DC
Switching state logical "0"
Switching state logical "1"
Position
> Lim. 1
< Lim. 2
> Lim. 2
1
1
0
0
0
1
*
max. 24 V AC / DC
max. 2 A
10 µm Gold (AU)
47

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tzidc-120Tzidc-110