Configuring the system
2.1 Service menu functions (DOS function)
Restoring the current HMI environment
The original HMI environment setting is undone, that is, the contents of the saved directories
are reloaded.
Procedure
While the PCU is ramping up (after switching the controller off and then on again):
1. Select the Service menu [hidden menu entry] in the Boot Manager.
2. Press key <4>: Start Windows (Service Mode)
X
Your Choice [1, 4, 5, 9]?
3. Press key <5>.
4. Enter one of the passwords for authorization levels 0 - 2.
2-6
The main menu is displayed:
The following menu is displayed:
PLEASE SELECT
1 Standard Windows (without starting SINUMERIK HMI)
4 Original SINUMERIK HMI environment
5 Current SINUMERIK HMI environment
9 Return to Main Menu
The system will ask you to enter the password:
Result:
The system will then restart automatically: The function is executed during the ensuing
start-up of Windows before the HMI system software is started.
Note
Restoration of the original settings for the HMI environment can also be canceled on the
Service desktop by starting the function "Current SINUMERIK HMI Environ".
Commissioning Manual, 10/2006, 6FC5397-0DP10-0BA0
PCU Basesoftware (IM6)