Table 3-65
EPSU2 - Technical Specifications
AC power
Frequency range
Connected output
Output power consumption/
nominal output
Mains/nominal voltage
UPS batteries
Battery operation:
Permitted batteries
Manufacturer/type num-
ber
Number of batteries
Size (Ah)
Nominal voltage
Overload protection
Nominal current
Overload protection
Ambient temperature
Humidity
Cooling
Protection
Housing dimensions (W x D
x H in mm)
Weight
Symbol
Personal safety, insulation
Grounding, shielding
3-154
EPSU2
S30122-K7221-X1
V39113-W5123-E891
Four batteries are supplied
built-in.
CSB/EVX-1270, Hitachi/HP6.5-12, Yuasa/NP6-12, Varta/
Noack 43720303, Sonnenschein/0719143200, Panasonic/
LCR12-7P
4 units, 12 V each
7 Ah
48 V (fully charged 54 V, discharge to 44 V)
Melting fuse 5 x 20 mm, 2.5 A/slow-blowing
Electronic current limiting circuit
In buildings, +5 to +45 °C (41 to 113 °F)
approx. 14.1 kg (incl. batteries) approx. 4.1 kg (without batter-
Protection class 1, output is floating against ground
HiPath 3000 V5.0, HiPath 5000 V5.0, Service Manual
S30122-K7221-X2
100 - 240 V AC
47 to 63 Hz
200 W
140 W
54.2 V
V39113-W5123-E891
Batteries are not included in
the scope of supply and must
be ordered separately.
2.5 A
95%, non-condensing
Natural convection
IP 21 (DIN 40050)
250 x 114 x 317
ies)
CE
EN60950 and IEC950
P31003-H3550-S403-4-7620, 02/05