Depending on the start mode function setting, if the fault trip is reset
and the OFF state is released by panel STOP function with run
signal being ON, the inverter may restart suddenly.
(Operate the inverter after ensuring personal safety.)
Failure to do so could lead to injury.
This parameter sets the starting operation for the case that a remote-control
set run signal is input when the power is turned ON.
The factory setting is "0"(Run).
When set to "1": OP stops immediately when the power is turned ON.
When set to "2": Operation starts after the wait time has elapsed after the
power is turned ON.
Data
Outline
setting
operation
value
Run
0
"OP" stop
1
Operate after
2
wait time
3
"OP" stop
[When power is turned ON with
run signal ON]
Power
supply
Run
signal
Operation
when "0" is set
Operation
when "1" is set
Operation
when "2" is set
Operation
when "3" is set
Note) The wait time can be set with parameter P25.
Operation starts immediately when the power is turned ON and the
low voltage level(LU level) is exceeded.
The inverter OP trips when the power is turned ON and the low voltage
level(LU level) is exceeded. Turn the start input signal OFF once, reset
the inverter and then turn the run signal ON again to resume operation.
The inverter starts when the power is turned ON, the low voltage level
(LU level) is exceeded and the wait time is passed.(The wait time is
set with parameter P25.)
The inverter OP trips when the power is turned ON and the low voltage
level(LU level) is exceeded. Turn the start input signal OFF once, reset
the inverter and then turn the run signal ON again to resume operation.
(This setting will function in the same manner as data "1" if the run
signal is ON when the power is turned ON. However, starting after
the wait time has elapsed is possible during normal startup.)
LU level
OP trip
Wait time
OP trip
Details of operation
[When run signal is turned ON after
power is turned ON]
Power
supply
Run
signal
Operation
when "0" is set
Operation
when "1" is set
Operation
when "2" is set
Operation
when "3" is set
LU level
Wait time
Wait time
49