Operation Control Status Monitor (R147); Frequency Setting (Dt 237 And 238); Operation Control Setting (R250); Fault Reset Command (Dt253), Emergency Stop Command (Dt255) - Panasonic AAD03011 Instruction Manual

Elevator door controller
Table of Contents

Advertisement

Operation control status monitor(R147 )
It indicates the operation control status of the inverter.
Relay No.
R1470
R1471
R1472
R1473
R1474
R1475
R1476
Frequency setting(DT 237 and 238)
In order to set frequency with communication control, parameter P09 is set to "6".
If registor No. 237 is written into the inverter, the memory inside the inverter does not work.
(Turn off the power supply of the inverter, the set data will not be saved.)
If registor No. 238 is written into the inverter, the memory inside the inverter will save it.
Use register No. 237 when frequency is changed frequently.
The inverter cannot be set in faulty case.
Operation control setting(R250 )
When performing the operation control with communication, set parameter P08 to "3".
If the inverter is in faulty case, fault will not reset even operation command is OFF ("0").
Use fault reset command (DT253), if fault reset is required.
Relay No.
R2500
R2501
Fault reset command(DT253)
The fault reset activates by writing "0 9696" in the register No.253.
The usable data is "0 9696" only.
he command is ignored when the inverter is operating properly.
Emergency stop command(DT255)
The emergency stop activates by writing "0 9696" in the register No.255.
The coast-to-stop function is performed displaying "AU" in the same operation as
the auxiliary fault input.
The usable data is "0 9696" only.
82
Name
OPEN command state
CLOSE command state
OPEN arrival command state
CLOSE arrival command state
Safety sensor input state
OPEN speed change command state
CLOSE speed change command state
Name
Run command state
Reverse run command state
Details
1: With command
0: No command
Details
1: ON command
0: OFF command