ABB AC500 Introduction Manual page 87

Scalable plc for individual automation
Table of Contents

Advertisement

The I/Os will have the following CPU addresses in the CPU mapping table:
Channels
Digital inputs 0-15
Digital inputs 0-7
Digital inputs 8-15
Single digital input 0
to
single digital input 7
Single digital input 8
to
single digital input 15
Digital configurable
inputs 16-31
Digital configurable
inputs 16-23
Digital configurable
inputs 24-31
Single digital
configurable input 16
to
single digital
configurable input 23
Single digital
configurable input 24
to
single digital
configurable input 31
Digital configurable
outputs 16-31
Digital configurable
outputs 16-23
Digital configurable
outputs 24-31
Single digital
configurable output 16
to
single digital
configurable output 23
Single digital
configurable output 24
to
single digital
configurable output 31
For more details concerning the I/O mapping, please refer to the AC500 User's manual.
____________________________________________________________________________________________________________
G1
Introduction to AC500
Address in
Comment
the mapping /
programming
software
%IW0
All the 16 digital inputs combined as Word from the
DC532 module
%IB0
All the 8 first digital inputs combined as Byte
%IB1
All the 8 following digital inputs combined as Byte
%IX0.0
Single digital input as a bit for the input 0 to the input 7
to
%IX0.7
%IX1.0
Single digital input as a bit for the input 8 to the input 15
to
%IX1.7
%IW1
All the 16 digital configurable I/Os as inputs in combined
as Word from the DC532 module
%IB2
All the 8 following digital configurable I/Os as inputs
combined as Byte
%IB3
All the 8 following digital configurable I/Os as inputs
combined as Byte
%IX2.0
Single digital configurable I/Os as input as a bit for the
input 16 to the input 23
to
%IX2.7
%IX3.0
Single digital configurable I/Os as input as a bit for the
input 24 to the input 31
to
%IX3.7
%QW0
All the 16 digital configurable I/Os as outputs combined
as Word from the DC532 module
%QB0
All the 8 following digital configurable I/Os as outputs
combined as Byte
%QB1
All the 8 following digital configurable I/Os as outputs
combined as Byte
%QX0.0
Single digital configurable I/Os as output as a bit for the
output 16 to the output 23
to
%QX0.7
%QX1.0
Single digital configurable I/Os as output as a bit for the
output 24 to the output 31
to
%QX1.7
1-85
AC500 / Issued: 07.2006

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents