LEDs on S500-FBP modules

All S500 modules have LEDs for the display of operating statuses and error messages. They indicate:
LED
Meaning
Input
digital input
analog input
Output
digital output
analog output
UP
process
voltage 24 V
DC via
terminal
PWR
24 V DC via
FBP
S-ERR
Sum Error
FBP
FBP
communication
I/O-Bus
I/O-Bus
communication
CH-ERR1
Channel Error,
error
CH-ERR2
messages in
CH-ERR3
groups (digital
CH-ERR4
or analog
inputs and
outputs
combined into
the groups 1,
2, 3, 4)
CH-ERR
Module Error
*)
*) All of the LEDs CH-ERR1 to CH-ERR4 (as far as they exist) light up together
For the meaning of the different LEDs and their behaviour when the system is running, please refer to
the S500 System Data of the S500 User's manual for further information.
____________________________________________________________________________________________________________
G1
Introduction to AC500
Color
LED = ON
yellow
input = ON
yellow
brightness depends on the value of the
analog signal
yellow
output = ON
yellow
brightness depends on the value of the
analog signal
green
voltage is present
green
voltage is present
red
serious error, data
exchange is
stopped, depends
on the behaviour of
the master
green
communication
between FBP and
FBP Interface
Module is running
green
communication
between FBP
Interface Module
and the I/O
modules is running
red
serious error within
the corresponding
red
group
red
red
red
error within the I/O
module
1-73
LED = OFF
LED flashes
input = OFF
--
--
output = OFF
--
--
voltage is missing
--
voltage is missing
--
no error
error (e.g. error
on one
channel, data
exchange is not
stopped
communication
during
between FBP and
initialization
FBP Interface
Module is broken
no communication
error on one I/O
between FBP
expansion
Interface Module
module (e.g.
and the I/O
one output
modules
short-circuited)
no error
error on one
channel of the
corresponding
group (e.g. one
output short-
circuited)
--
--
AC500 / Issued: 07.2006

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents