Commissioning
3.3.4

Communication objects Group x

It is possible to parameterize status messages. The communication objects change accordingly.
Depending on the parameterization, the communications objects change, e.g. for group 1:
No. 30 and 31 separate communication objects or common communication object no. 30
No. 32 and 33 separate communication objects or common communication object no. 32
No.
30
Using this communication object, the lighting group is switched on or off with the predefined brightness value
window Gx
Telegram value:
When an ON telegram is received, the parameter settings define if a predefined brightness value or the value before switch
off is set.
If the lighting group is switched on with any brightness value and it receives a renewed ON telegram, the parameterized
brightness value of the switch-on value is set. Any Burn-in function currently active has a higher priority, so that, under
certain circumstances, individual devices can only assume a brightness of 100 % or OFF.
Other parameter settings define whether the switch-on value is dimmed to, or whether it takes immediate effect. Switch on
values, which are above or below the maximum/minimum brightness values, are replaced by the corresponding brightness
values.
If one of the additional functions Slave or Staircase lighting is activated, this function is triggered with an ON telegram
(value 1) and the respective timing is started. An inversion is not intended.
It is possible to parameterize that the switch status is fed back via the communication object Status switch or via
Switch/Status. Generally, the status messages use a separate communication object Status switch for this purpose. This
can be parameterized in the
30
The communication object is enabled if, in the
switching state is parameterized with Yes: via object "Switch/Status".
This communication object has the same functions and properties as the communication object Switch. The status is
additionally fed back. Additionally, the value of the communication object is also updated if it is not sent on the KNX.
Telegram value:
144 2CDC 507 100 D0202 | DLR/S 8.16.1M
Function
Switch
Group, page 67).
0 = OFF: Lighting group switched off
1 = ON: Lighting group switched on
Parameter window - Gx
Switch/Status
0 = OFF or OFF and status: Lighting group switched off
1 = ON or ON and status: Lighting group switched on
Note
If several KNX group addresses are assigned to the communication object Switch/Status, the status
address should be set as the sending address. In a KNX group with several status messages, it is useful to
allow just a single group member to feed back the status.
Object name
Group x
Status, page 77.
Group x
Status, page 77, 
the parameter Status response of
Parameter window - Gx
Data type
Flags
1 bit
C, W
DPT 1.001
(Parameter
1 bit
C, R, W, T
DPT 1.001