Mounting and installation

The DALI Light Controller DLR/S 8.16.1M is a modular installation device for quick installation in the
distribution board on 35 mm mounting rails to EN 60 715. The installation position can be selected as
required.
The electrical connection is implemented using push-in screw terminals. The connection to the KNX is
implemented using a supplied push-in screw terminal. The terminal designations are located on the
housing.
Accessibility of the devices for the purpose of operation, testing, visual inspection, maintenance and repair
must be provided compliant to VDE 0100-520.
Commissioning requirement
In order to commission the DLR/S, a PC with ETS and a KNX interface, e.g. USB or IP, are required.
The DLR/S is ready for operation after connection to the bus voltage.
The assignment of DALI devices to lighting groups, which are controlled in the KNX, is undertaken in the
Software Tool.
For more information see: online help, Software Tool
The device is ready to operate when the KNX voltage and the light controller supply voltage are applied.
Mounting and start-up may only be carried out by electrical specialists. The appropriate standards,
guidelines, regulations and specifications for the appropriate country should be observed when planning
and setting up electrical installations and security systems for intrusion and fire detection.
Protect the device from moisture, dirt and damage during transport, storage and operation.
Only operate the device within the specified technical data!
The device should only be operated in an enclosed housing (distribution board)!
The voltage supply to the device must be switched off before mounting work is performed.
To avoid dangerous touch voltages which originate through feedback from differing phase conductors,
all poles must be disconnected when extending or modifying the electrical connections.
The Light Sensor LF/U 2.1 is optimized for ceiling installation in a commercially available 60 mm flush
mounted box. The brightness detection can be influenced with the supplied fibre-optic rods. Refer to the
Polar diagram LF/U
The brightness sensor should be situated so that it is not influenced directly or indirectly by the lamps.
Pay attention to reflections, e.g. from window sills, mirrored or glass surfaces.
Danger
2.1, page 22 for the detection range.
DLR/S 8.16.1M | 2CDC 507 100 D0202 23