Dali light controller dlr/s 8.16.1m
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
No.
36
This communication object is enabled if, in the
control function is enabled.
Lighting group x can be forcibly operated via this communication object (e.g. by a higher-level control). The value of the
communication object directly defines the forced position of the lighting group:
Telegram value:
Incoming telegrams during Forced operation are not executed, but are, however, evaluated in the background (dimming
processes are not considered). After the enabling of the lighting group, the incoming telegrams are processed again. When
Forced operation is removed, the lighting group is set with the brightness value calculated in the background. A previous
Light control or Slave function is recommenced (in standby). The Staircase lighting function is started in the dimming
phase.
If the lighting group had control before forced operation, lighting control will be reassumed after forced operation.
After a download, the communication object Forced operation has the value 0.
The forced operation is not activated.
Forced operation has a higher priority than blocking a lighting group.
The state of the KNX bus voltage can be parameterized.
For further information, see:
36
This communication object is enabled if, in the
control function is enabled.
Lighting group x can be forcibly operated via this communication object (e.g. by a higher-level control). The value of the
communication object directly defines the forced position of the lighting group:
Telegram value:
The brightness value of the lighting group is calculated with an incoming telegram during forced operation, but is not
however displayed. Dimming speeds are not considered with the calculation, i.e. in the background, the immediate end
values are stored. After the completion of forced operation, the brightness values calculated in the background are set.
A dim, scene or staircase lighting recall will not be reinitiated.
If the DLR/S had control before Forced operation, light control will be reassumed after Forced operation with the switch-on
value.
After a download, the communication object Forced operation has the value 0.
The forced operation is not activated.
Forced operation has a higher priority than blocking a lighting group.
The State on bus voltage recovery can be parameterized.
For further information, see:
148 2CDC 507 100 D0202 | DLR/S 8.16.1M
Function
Forced operation
0 or 1 = The lighting group is not forced operated, an existing forced operation is rescinded.
2 =
The lighting group is forcibly switched off. Forced operation is active.
3 =
The lighting group is switched on forcibly with the parameterized brightness
value. Forced operation is active.
Parameter window - Gx
Forced operation
0 = The lighting group is not forced operated, a forced operation is rescinded.
1 = The lighting group is operated forcibly and switched on with the parameterized brightness
value. Forced operation is active.
Parameter window - Gx
Object name
Group x
Parameter window - Gx
Functions, page 86, the Forced operation 2 bit
Functions, page 86.
Group x
Parameter window - Gx
Functions, page 86, the Forced operation 1 bit
Functions, page 86.
Data type
Flags
2 bit
C, R, W
DPT 2.001
1 bit
C, R, W
DPT 1.003