Reading Module Specific Information - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Reading module specific information

UNIINFRD(P)
RnPCPU
RnPCPU
RnCPU RnENCPU
(Process)
(Redundant)
These instructions read the specified points of module information.
Ladder
(H)
(d)
(n)
FBD/LD
EN
ENO
H
d
n
■Execution condition
Instruction
UNIINFRD
UNIINFRDP
Setting data
■Description, range, data type
Operand
Description
(H)
Start I/O number (first three digits in four-digit hexadecimal
representation) of an information read target module
(d)
Start device for storing module information
(n)
Number of read data points
EN
Execution condition
ENO
Execution result
*1 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
■Applicable devices
Operand
Bit
X, Y, M, L,
J\
SM, F, B, SB,
FX, FY
(H)
(d)
(n)
RnSFCPU RnSFCPU
(Standard)
(Safety)
Execution condition
Word
T, ST, C, D, W,
U\G, J\,
SD, SW, FD, R,
U3E\(H)G
ZR, RD
ST
ENO:=UNIINFRD(EN,H,n,d);
ENO:=UNIINFRDP(EN,H,n,d);
Range
Data type
0H to FFH
16-bit unsigned binary
Word
0 to 256
16-bit unsigned binary
Bit
Bit
Double word Indirect
Z
LT, LST,
LZ
LC
7 APPLICATION INSTRUCTIONS
Data type (label)
ANY16
*1
ANY16
ANY16
BOOL
BOOL
Constant
Others
specification
K, H E
$
7.27 Module Access Instructions
7
1067

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents