Resetting trigger logging

LOGTRGR
RnPCPU
RnCPU RnENCPU
(Process)
This instruction resets the trigger condition of the specified logging setting number.
Ladder
(s)
FBD/LD
EN
ENO
s
■Execution condition
Instruction
LOGTRGR
Setting data
■Description, range, data type
Operand
Description
(s)
Logging setting number
EN
Execution condition
ENO
Execution result
■Applicable devices
Operand
Bit
X, Y, M, L,
SM, F, B, SB,
FX, FY
(s)
Processing details
• This instruction resets the LOGTRG instruction of the logging setting number specified by (s). The instruction disables the
LOGTRG instruction of the specified trigger logging setting number.
• The LOGTRGR instruction turns off the special relays (logging completion, logging trigger, and after logging trigger) with
the logging setting number in the device specified by (s).
• If the instruction is executed while buffer data is saved to an SD memory card, the execution of the instruction is made to
wait until all data is saved completely.
Operation error
Error code
Description
(SD0)
3405H
The value set to (s) is out of the range, 1 to 10.
7 APPLICATION INSTRUCTIONS
1078
7.29 Logging Instructions
RnPCPU
RnSFCPU RnSFCPU
(Redundant)
(Standard)
(Safety)
Execution condition
Word
J\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
ST
ENO:=LOGTRGR(EN,s);
Range
1 to 10
Double word
U\G, J\,
Z
LT, LST,
U3E\(H)G
LC
Data type
Data type (label)
16-bit signed binary
ANY16
Bit
BOOL
Bit
BOOL
Indirect
Constant
specification
LZ
K,
H
Others
E
$