Transferring single-precision real number

EMOV(P)
RnPCPU
RnPCPU
RnCPU RnENCPU
(Process)
(Redundant)
These instructions transfer single-precision real number data to the specified device.
Ladder
(s)
(d)
FBD/LD
EN
ENO
s
d
■Execution condition
Instruction
EMOV
EMOVP
Setting data
■Description, range, data type
Operand
Description
(s)
Data to be transferred or start device containing the data to
be transferred
(d)
Start device for storing transferred data
EN
Execution condition
ENO
Execution result
■Applicable devices
Operand
Bit
X, Y, M, L,
J\
SM, F, B, SB,
FX, FY
(s)
(d)
Processing details
• These instructions transfer the single-precision real number data stored in the device specified by (s) to the device
specified by (d).
(s)+1
(s)
Transfer
4.23542
Single-precision real number
Operation error
There is no operation error.
RnSFCPU RnSFCPU
(Standard)
(Safety)
Execution condition
Word
T, ST, C, D, W,
U\G, J\,
SD, SW, FD, R,
U3E\(H)G
ZR, RD
(d)+1
(d)
4.23542
Single-precision real number
ST
ENO:=EMOV(EN,s,d);
ENO:=EMOVP(EN,s,d)
Range
Data type
-126
128
|(s)|<2
0, 2
Single-precision real
number
Single-precision real
number
Bit
Bit
Double word Indirect
Z
LT, LST,
LZ
LC
7 APPLICATION INSTRUCTIONS
Data type (label)
ANYREAL_32
ANYREAL_32
BOOL
BOOL
Constant
Others
specification
K, H E
$
7.9 Real Number Instructions
7
769