Supplementary system components and encoder system integration
7.2 Terminal Module 31 (TM31)
7.2.3.3

X500 and X501 DRIVE-CLiQ interface

Table 7-6
DRIVE-CLiQ interface X500
Pin
1
2
3
4
5
6
7
8
A
B
Blanking plate for DRIVE-CLiQ interface: Molex, order number: 85999-3255
7.2.3.4

Electronics power supply X524

Table 7-7
Terminals for the electronics power supply
Terminal
+
+
M
M
Max. cross-section that can be connected: 2.5 mm²
Type: Screw terminal 2 (see Appendix A)
Note
The two "+" and "M" terminals are jumpered in the connector. This ensures the supply
voltage is looped through.
The current consumption increases by the value for the DRIVE-CLiQ node and digital
outputs.
7-8
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
GND (0 V)
Designation
Electronics power supply
Electronics power supply
Electronic ground
Electronic ground
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
Power supply
Electronic ground
Technical specifications
Voltage: 24 V DC (20.4 V – 28.8 V)
Current consumption: max. 0.5 A
Max. current via jumper in connector:
20 A at 55 °C
Manual, (GH6), 03/2006 Edition, 6SL3097-2AL00-0BP0