Supplementary system components and encoder system integration
7.2 Terminal Module 31 (TM31)
7.2.3.6

Digital inputs X530

Table 7-9
Screw terminal X530
Terminal
1
2
3
4
5
6
Max. cross-section that can be connected: 1.5 mm²
Type: Screw terminal 1 (see Appendix A)
1) DI: digital input; M: electronic ground; M2: Ground reference
Notice
An open input is interpreted as "low".
To enable the digital inputs to work, terminal M2 must be connected. This can be done as
follows:
1) Route the reference ground of the digital inputs (with the other cable) and connect it to
M2.
2) Jumper terminal M and M2 directly
(the electrical isolation for these digital inputs is therefore removed).
7-10
Designation
1)
DI 4
DI 5
DI 6
DI 7
M2
M
Technical specifications
Voltage: -3 V to 30 V
Typical current consumption: 10 mA at 24 V DC
Isolation: The reference potential is terminal M2
Signal propagation times:
L → H approx. 50 μs
H → L: approx. 100 µs
Level (incl. ripple)
High level: 15 V to 30 V
Low level: -3 V to 5 V