Indoor unit digital inverter: compact 4-way cassette type; concealed duct type; ceiling type
Hide thumbs Also See for RAV-SM304MUT-E:
Table of Contents

Advertisement

No.
Part name
Multi blade fan
motor
AMP Air Conditioning
Procedure
1. Remove the suction grille.
2. Remove the connector of the fan
motor from P .C. board.
3. (SM802, SM1102, SM1402CT-E only)
Remove the set screw (1 position) to
fixing and reinforcing bar.
(Slide the reinforcing bar toward
arrow side on the left figure.)
4. Push the fan cover fixing hooks
(2 positions) forward fan cover side
and remove the fan cover.
5. (SM1102, SM1402CT-E only)
Remove the hexagon head screws (2
positions) to fix bearing and the
bearing.
6. Remove the hexagon head screw of
fixing fan motor and fan motor holder
then the assembly removed from the
main unit.
7. Loosen the sets crew of the multi
blade fan using hexagon wrench.
8. Pull the multi blade fan towered fan
case side. Then fans come off.
Screws
(Fixing reinforcing bar and main unit)
Fan cover fixing hook
Hexagon head screws
(Fixing bearing and main unit)
Fan motor holder
Set screw of multi blade fan
– 101 –
www.ampair.co.uk | sales@ampair.co.uk
Remarks
Reinforcing bar
Fan cover (Lower side)
Bearing
Bearing
Fan motor
Fan motor
Hexagon screws
(Fixing fan motor and main unit)
Multi blade fan
4 -3