Toshiba RAV-SM304MUT-E Service Manual page 103

Indoor unit digital inverter: compact 4-way cassette type; concealed duct type; ceiling type
Hide thumbs Also See for RAV-SM304MUT-E:
Table of Contents

Advertisement

No.
Part name
ˆ
Horizontal
louver
TC, TCJ sensor
Š
Heat
exchanger
AMP Air Conditioning
Procedure
1. Push the louver holder toward arrow
direction of right figure, and pull out
the center shaft (SM562, SM802 :
1 position, SM1102, SM1402 :
2 positions) from louver holder.
2. Pull off the left and right chaft of
horizontal louver.
1. Remove the drain pan.
2. Remove the set screws (4 positions)
and heat exchanger support.
3. Pull out the sensor is inserted into
pipe of the heat exchanger.
1. Take down the main unit and then
treat the heat exchanger on the floor.
2. Remove the drain pan.
3. Remove the set screws (6 positions)
of fixing heat exchanger and main
unit.
Louver holder
Heat exchanger
Screws
(Fixing heat exchanger and main unit)
– 103 –
www.ampair.co.uk | sales@ampair.co.uk
Remarks
Shaft of
horizontal louver
Screws
(Fixing heat exchanger support)
Heat exchanger support
8 -1
9 -3
10 -3