Toshiba RAV-SM304MUT-E Service Manual page 59

Indoor unit digital inverter: compact 4-way cassette type; concealed duct type; ceiling type
Hide thumbs Also See for RAV-SM304MUT-E:
Table of Contents

Advertisement

[F02 error]
Is connection of TC sensor connector
(CN101 on Indoor P.C. board) correct?
YES
Are characteristics of
TC sensor resistance value normal?
YES
Check indoor P.C. board (MCC-1402).
Defect → Replace
[F01 error]
Is connection of TCJ sensor connector
(CN102 on Indoor P.C. board) correct?
YES
Are characteristics of
TCJ sensor resistance value normal?
YES
Check indoor P.C. board (MCC-1402).
Defect → Replace
AMP Air Conditioning
NO
NO
∗ Refer to Charqacteristics-2.
NO
NO
∗ Refer to Charqacteristics-2.
Correct connection of connector.
Correct connection of connector.
– 59 –
www.ampair.co.uk | sales@ampair.co.uk
Replace TC sensor.
Replace TCJ sensor.