Configuring Iec101 Device Properties - ABB COM600 User Manual

Station automation
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

1MRS756703
3.4.4.
Station Automation COM600
User's Manual
Property / Para-
Value or Value range/ Default
meter
Receive Interrupt
0...255
Delay
Response Timeout
0...255
Default: 2
RTS Keep Up Delay
0...20
Default: 1
RTS Keep Up Pad-
0...255
ding Characters
Default: 0
Time Synchroniza-
0...65535
tion Interval
Default: 15
Transmission Wait
0...65535
Delay
Default: 15
Polling
Polling Delay
0...65535
Default: 50
Polling Limit
2...100
Default: 10
Polling Period
1...255
Default: 10
Reply Poll Count
1...20
Default: 1
Secondary Polling
0...100
Limit
Default: 0

Configuring IEC101 Device properties

Table 3.4.4-1 lists the configurable properties for IEC101 Device and value ranges for
these properties. The actual configuration by using SAB600 is performed as described
in 3.4.1, General about configuring objects.
Table 3.4.4-1 IEC101 Device properties
Name
Basic
Description
Defines the delay after which the receiver
of line is enabled after a message has
been issued.
The time that IEC link waits for the end of
the received message in seconds.
The number of characters for calculating
delay for resetting RTS signal.
The number of padding characters inser-
ted to the end of telegram to delay the
resetting of RTS signal.
Time synchronization interval in seconds.
Delay in milliseconds between receiving
CTS signal and start of transmission.
Delay between polling messages.
Limits the number of successive polls of
station.
The polling frequence of suspended sta-
tion.
The reply polling specifies the number of
successive polls to a station where com-
mand has been sent.
Limits the number of successive class 2
polls of station. Value should be smaller
than value of Polling Limit.
Value/Value range
IEC 60870-5-101
Master (OPC) 3.3
Description
27