1MRS756703
3.4.5.16.
Station Automation COM600
User's Manual
Property/ Para-
Value or Value range/ Default
meter
Min
Default: 0

Controllable single point (SPC)

Table 3.4.5.16-1 Configurable SPC properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
SPC
Class
Sub-Type
Sub Type
Indication only
IEC style command
Default: IEC style command
Addresses
Command Address
0...16777215
Default: 0
DirectOperate
True
False
Default: False
DMCD-Type
Single command
Double command
Indication Address
OPC Alarm and
Event
Command Tracking
DirectOperate
Event
TapchangerAutoManualOpera-
tion
Default: None
Indication Event
Default: None
Scale and Unit
IEC 60870-5-101
Master (OPC) 3.3
Description
Minimum value for measurement.
Description
Common data class according to IEC
61850.
Object subtype.
IEC address for command.
DirectOperate description.
DMCD-Type to be used.
IEC address for indication.
Command tracking event used with this
data object.
Indication event used with this data object.