ABB COM600 User Manual page 63

Station automation
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

1MRS756703
Station Automation COM600
User's Manual
Transmission mode for application data
Mode 1 (The least significant octet first), as defined in clause 4.10 of IEC 870-5-4, is
used exclusively in this companion standard
Common address of ASDU (system-specific parameter)
One octet
Information object address (system-specific parameter)
One octet
Two octets
Three octets
Cause of transmission (system-specific parameter)
One octet
Selection of standard ASDUs
Process information in monitor direction (station-specific parameter)
<1>
:=Single-point information
<2>
:=Single-point information with time tag
<3>
:=Double-point information
<4>
:=Double-point information with time tag
<5>
:=Step position information
<6>
:=Step position information with time tag
<7>
:=Bitstring of 32 bit
<8>
:=Bitstring of 32 bit with time tag
<9>
:=Measured value, normalized value
<10>
:=Measured value, normalized value
with time tag
<11>
:=Measured value, scaled value
<12>
:=Measured value, scaled value with
time tag
<13>
:=Measured value, short floating point
value
<14>
:=Measured value, short floating point
value with time tag
<15>
:=Integrated totals
<16>
:=Integrated totals with time tag
IEC 60870-5-101
Master (OPC) 3.3
Two octets
structured
unstructured
Two octets (with originator address)
M_SP_NA_1
M_SP_TA_1
M_DP_NA_1
M_DP_TA_1
M_ST_NA_1
M_ST_TA_1
M_BO_NA_1
M_BO_TA_1
M_ME_NA_1
M_ME_TA_1
M_ME_NB_1
M_ME_TB_1
M_ME_NC_1
M_ME_TC_1
M_IT_NA_1
M_IT_TA_1
63