Protection Activation Information (Act) - ABB COM600 User Manual

Station automation
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

IEC 60870-5-101
Master (OPC) 3.3
3.4.5.2.
32
Station Automation COM600
User's Manual
Property/Para-
Value or Value range/ Default
meter
Indication Event for
Phase C

Protection activation information (ACT)

Table 3.4.5.2-1 Configurable ACT properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
ACT
Class
Addresses
General Address
0...16777215
Default: 0
Neutral address
0...16777215
Default: 0
Phase A Address
0...16777215
Default: 0
Phase B Address
0...16777215
Default: 0
Phase C Address
0...16777215
Default: 0
OPC Alarm and
Event
Indication Event for
General
Indication Event for
Neutral
Indication Event for
Phase A
Indication Event for
Phase B
Indication Event for
Phase C
Description
Indication event used with phase C.
Description
Common data class according to IEC
61850.
IEC Address for general indication.
IEC Address for neutral (0 = Not in use).
IEC Address for phase A (0 = Not in use).
IEC Address for phase B (0 = Not in use).
IEC Address for phase C (0 = Not in use).
Indication event used with general phase.
Indication event used with neutral phase.
Indication event used with phase A.
Indication event used with phase B.
Indication event used with phase C.
1MRS756703