IEC 60870-5-101
Master (OPC) 3.3
28
Station Automation COM600
User's Manual
Name
Diagnostics Enabled
In Use
Simulation Mode
Addresses
Polling Address
Station Address
Communication control
Activation Reply Timeout
Activation Termination Timeout
Activation Termination waited
Disable automatic GI sending
during communication initializa-
tion
Value/Value range
True
False
Default: False
In use
Not in use
Default: In use
True
False
Default: False
0...255 or
Default: 1
0...255 or
Default: 1
0...255
Default: 10
0...255
Default: 60
True
False
Default: True
True
False
Default: False
1MRS756703
Description
Specifies whether diagnostic
AE events are sent for the sta-
tion or not.
Controls whether the station
communication is initially in use
or not.
Specifies whether the device is
in simulation mode.
The link address of the IEC
60870-5-101 slave station.
The station address of the IEC
60870-5-101 slave station (the
common address of ASDU).
The maximum time the IEC
master station waits for an
activation confirmation mes-
sage from the IEC slave.
The maximum time the IEC
master station waits for an
activation termination message
from the IEC slave.
The waiting of the activation
termination message. With
value True, the termination is
waited according to the Activa-
tion Termination Timeout prop-
erty. With value False, no
activation termination is
required from the slave IED.
Sending of the general interrog-
ation command during commu-
nication initialization. When
false, a general interrogation
command is always sent when
the communication with the
slave is established or
recovered. When true, general
interrogation is not sent.