1MRS756703
5.
5.1.
5.2.
5.2.1.
5.2.2.
Name
Type
stVal
BOOLEAN
q
Quality
t
TimeStamp
d
Description
Station Automation COM600
User's Manual

Technical reference

About this section

This section provides reference information about the following issues:

IEC 61850 data modeling

Attributes
Status codes
IEC 61850 data modeling

General about IEC 61850 data modeling

The relationship between the IEC 61850 data modeling and IEC101 OPC Server is
described in this section.
For each data class, there is a table giving a detailed description about the relation between
the IEC101 data and IEC 61850 data object attributes and services. The tables also
describe how the data is presented on the OPC Server name space.
The columns in the tables have the following content types:
Name specifies the OPC item name of the attribute/service.
Type specifies the IEC 61850 type of the attribute.
Value/ Value range specifies the allowed values and ranges of the attribute/service.
Mandatory/Optional specifies whether the attribute is considered as mandatory or
optional according to the IEC 61850 standard.
IEC101 information element specifies the IEC101 information element related to
the attribute/service.
OPC data types specify the OPC data type used for the OPC item.

Single point status (SPS)

SPS represents DMCD M_SP_NA_1, M_SP_TA_1, M_SP_TB_1.
Value/Value range
TRUE | FALSE
Text
Mandat-
Protocol informa-
ory/Optional
tion element
M
SPI(0=ON, 1=OFF)
M
BL, SB, NT, IV
M
CP24Time2a
CP56Time2a
O
IEC 60870-5-101
Master (OPC) 3.3
OPC data types
VT_BOOL
VT_I4
VT_DATE
VT_BSTR