ABB COM600 User Manual page 64

Station automation
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

IEC 60870-5-101
Master (OPC) 3.3
64
Station Automation COM600
User's Manual
<17>
:=Event of protection equipment with
time tag
<18>
:=Packed start events of protection
equipment with time tag
<19>
:=Packed output circuit information of
protection equipment with time tag
<20>
:=Packed single point information with
time tag
<21>
:=Measured value, normalized value
without quality descriptor
<30>
:=Single-point information with time tag
CP56Time2a
<31>
:=Double-point information with time tag
CP56Time2a
<32>
:=Step position information with time tag
CP56Time2a
<34>
:=Measured value, normalized value
with time tag CP56Time2a
<36>
:=Measured value, short floating point
value with time tag CP56Time2a
<37>
:=Integrated totals with time tag
CP56Time2a
<128
:=Parameter byte string
<130>
:=101 Encapsulated SPA bus reply
message
Process information in control direction (station-specific parameter)
<45>
:=Single command
<46>
:=Double command
<47>
:=Regulating step command
<48>
:=Set point command, normalized value
<49>
:=Set point command, scaled value
<50>
:=Set point command, short float point
value
<51>
:=Bitstring of 32 bit
<131>
:=Parameter byte string
<133>
:=101 Encapsulated SPA bus message
System information in monitor direction (station-specific parameter)
<70>
:=End of initialization
1MRS756703
M_EP_TA1
M_EP_TB1
M_EP_TC_1
M_PS_NA_1
M_ME_ND_1
M_SP_TB_1
M_DP_TB_1
M_ST_TB_1
M_ME_TD_1
M_ME_TF_1
M_IT_TB_1
M_SR_NA_1
M_SB_NA_1
C_SC_NA_1
C_DC_NA_1
C_RC_NA_1
C_SE_NA_1
C_SC_NB_1
C_SC_NC_1
C_BO_NA_1
C_SR_NA_1
C_SB_NA_1
M_EI_NA_1

Advertisement

Table of Contents
loading