Setting Radio Parameters
The TransNET 900 radio has certain parameters which are set in the MDS factory.
The radio address ADDR = xx, where xx is the same number for all radios in the
system The address appears on the radio itself.
Mode - either MASTER or REMOTE (Slave). The mode setting appears on the radio
itself.
Baud rate (factory default = 9600 8N1)
These radio settings are determined in the MDS factory and are not generally changed by the
user. If it is necessary to change these settings, refer to the TransNET 900 radio
documentation.
RTU Configuration
The RTU port is configured using the ACE3600 STS as follows:
Procedure 21-29 How to Configure the ACE3600 Port for the TransNET 900 Radio
1.
In the ACE3600 STS click on the desired site, and open the site view.
2.
In the Port Tab, click on the on-board or plug-in port through which the RTU will
communicate with the TransNET radio.
3.
Confirm that the port parameters and data speed are as shown in the screen below.
Note: If the baud rate of the radio is not the default value (9600), the baud rate of the port
should be configured accordingly.
4.
Define desired links.
5.
Save the changes.
Figure 21-50 RTU Site Configuration for TransNET Radio– Port Type Parameters
21-59