ABB i-bus
EIB / KNX
3.2.2
Parameter window
"Channel A – Voltage,
current and resistance"
Commissioning
Fig. 10: Parameter window "Channel A – Voltage, current and resistance"
Use channel
Options:
no/yes
This parameter determines the use of channel A.
Sensor output
Options:
0–1 V/0–5 V/0–10 V/1–10 V
0–20 mA/4–20 mA/0–1000 ohm/
Floating contact interrogation /
PT100 2-conductor technology – 30...+ 70 °C/
PT100 2-conductor technology – 200...+ 800 °C
This parameter is used to set the Sensor output. The data can be found
in the technical documentation of the sensor manufacturer.
Send output value as
Options:
1-byte [0...+ 255]
1-byte [– 128...+ 127]
2-byte [0...+ 65,535]
2-byte [– 32,768...+ 32,767]
2-byte [EIB floating point]
4-byte [IEEE floating point]
This parameter is used to define the format in which the Output value should
be sent. If the "1-byte [0...+ 255]" option is selected, for example,
the Output value is sent as a 1-byte value.
If the 2-byte [EIB floating point] or 4-byte [IEEE floating point] option is set,
a further parameter appears at the bottom of the parameter window.
What is the output value?
The output value designates the value which Analogue Input sends
to the bus. Analogue Input records a sensor value, converts it according
to the set parameters and sends it to the bus.
13