ABB i-bus
EIB / KNX
Commissioning
Send output value
Options:
on request
after a change
cyclically
after a change and cyclically
This parameter is used to define how the Output value should be sent.
If the on request option is selected, the "Request output value – Channel A"
communication object appears.
As soon as a "1" is received at this communication object, the current out-
put value is sent once to the "Output value – Channel A" communication
object.
In the case of the after a change, cyclically and after a change and cyclically
options, further parameters appear.
Output value is sent, every
Options:
5 s/10 s/30 s/1 min/5 min/10 min/30 min/1 h/6 h/12 h/24 h
This additional parameter is used to set the interval for cyclical sending.
Output value is sent after x % deviation from the output range
Options:
1/2...100
This parameter is used to define what percentage change in the output
range should cause the output value to be sent.
If 2 is selected as the option, the output value is sent after a 2% change
in the output range.
What is the output range?
The output range is determined by the setting options for the upper and
lower measuring limits. The difference between the upper and lower
measuring limit forms the output range.
Example: If the lower measuring limit for the sensor (0...1000 ohm) is set
to 10% (100 ohm) and the upper measuring limit is set to 90% (900 ohm),
the output range (900 ohm – 100 ohm) = 800 ohm.
2% of 800 ohm = 16 ohm.
17