9 Configuring TFIO interfaces
To scan and transmit data using the TFIO modules, the RMC TFIO interface must be
enabled. Connected TFIO modules are detected only when the interfaces are
enabled.
IMPORTANT NOTE: The TFIO-A interface is enabled by default. The
TFIO-B is disabled by default.
To verify or enable communication with TFIO modules:
1.
On the navigation tree, under the I/O System:
a.
If modules were installed in TFIO-A, select TFIO A Modules (Figure 27).
The TFIO Module List tab displays:
i.
Verify all TFIO modules connected and their type are listed.
b.
If modules were installed in TFIO-B, select TFIO-B Modules:
i.
Change TFIO-B Interface to Enabled.
ii.
Click Send.
iii.
Verify all TFIO modules connected and their type are listed.
30 | 2105551-001 rev. AC
Figure 27: TFIO A configuration