3.
Select the Type from the drop-down list. Digital Input (Voltage) is the default.
4.
Configure each Digital I/O port as appropriate:
a.
For digital input mode, select the low and high threshold voltage.
b.
For digital output mode, select the current value and the initial value.
5.
Click Send.
8.5

Pulse input configuration

Each pulse input has a debounce filter. Without debounce, the PI operates at a
frequency range of 0 to 20 kHz. With debounce, the frequency range is 0 to 100 Hz.
To configure the pulse input:
1.
Select I/O System on the navigation tree.
2.
Select the Pulse Inputs tab (Figure 26).
3.
Go to the Debounce area of the screen.
4.
Select On if debounce is required. Set this for each PI port if debounce is
needed.
5.
Click Send.
Figure 26: Pulse input configuration
2105551-001 rev. AC | 29