Profinet Gsdml - Siemens SINAMICS S120 Series Function Manual

Hide thumbs Also See for SINAMICS S120 Series:
Table of Contents

Advertisement

Topology rules
Topology rules for RT
● A topology can be, but need not be configured for RT. If a topology has been configured,
the devices must be wired in accordance with the topology.
● Otherwise, the wiring between devices is entirely optional.
Topology rules for IRT
● Mixed operation is not supported by STEP 7 V5.4 SP4, i.e. IRT "high performance"
cannot be combined with IRT "high flexibility" in the same synchronization domain.
● A synchronization domain with IRT "high performance" can contain a maximum of one
IRT "high performance" island. "Island" means that the devices must be interconnected to
match the configured topology. A synchronization master must be positioned in the
relevant island.
● IRT "high flexibility" is subject to the same topology rules as for IRT "high performance",
the only exception being that a topology does not need to be configured. However, if a
topology has been configured, the devices must be wired to match the topology.
Device selection in HW Config
Hardware catalog
The drive unit from the appropriate device family entry in the hardware catalog must be
configured. For the real-time class IRT, these are all entries as of firmware version V2.5.
GSDML
GSDML files for devices which contain IRT as of firmware version V2.5.
5.3

PROFINET GSDML

SINAMICS S120 supports the GSDML version: "PROFINET GSDML" to embed the
converter in a PROFINET network.
PROFINET GSDML allows standard telegrams to be combined with a PROFIsafe telegram –
and if required, a telegram extension. Each of the modules has four subslots: The Module
Access Point (MAP), the PROFIsafe telegram, a PZD telegram to transfer process data and
where necessary, a telegram for PZD extensions. Example:
GSDML-V2.31-Siemens-Sinamics_S_CU3x0_20160101.xml
You can download GSDML files from the following Siemens Internet address:
PROFINET GSDML (https://support.industry.siemens.com/cs/ww/en/view/49217480)
The GSDML files on the memory card are saved in the following location:
..\SIEMENS\SINAMICS\DATA\CFG\PNGSD.ZIP
Communication
Function Manual, 12/2018, 6SL3097-5BD00-0BP0
Communication via PROFINET IO
5.3 PROFINET GSDML
129

Advertisement

Table of Contents
loading

Table of Contents