Advertisement

5.13.3 Liquid level measurements on closed tanks and
non condensable fluids (dry leg)
— Mount the transmitter at the same height or below the
lowest level to be measured.
— Connect the + (H) side of the transmitter to the bottom of
the tank.
— Connect the - (L) side of the transmitter to the upper part
of the tank, above the maximum level of the tank.
Figure 28: Level measurement on closed tank with dry leg
5.13.4 Liquid level measurement with closed tanks and
condensable fluids (wet leg)
— Mount the transmitter at the same height or below the
lowest level to be measured.
— Connect the + (H) side of the transmitter to the bottom of
the tank.
— Connect the - (L) side of the transmitter to the upper part
of the tank.
— Fill the vertical section of the connecting line to the upper
part of the tank with a compatible liquid through the
dedicated filling tee.
26 OI/266/PB-EN Rev. E | 2600T Series Pressure transmitters
Figure 29: Level measurement on closed tank with wet leg
5.13.5 Liquid level measurement with open tanks
— Mount the transmitter at the same height or below the
lowest level to be measured.
— Connect the + (H) side to the bottom of the tank.
— Vent the "–" (L) side of the transmitter to the atmosphere
(in this case a gauge pressure is shown; the (L) side is
already vented to the atmosphere).
Figure 30: Level measurement on open tank with P style transmitter