12.5 Savings

In order to keep a valid device setting to be used as reference
when a valid condition has to be recovered in case of wrong
operations, it is possible save all the above calibrations as
Factory or User calibrations and the complete device
configuration.
The possible savings are the following and are executed writing
the proper code in the PB_SAVINGS, for details refer to the
APPENDIX A - Device Mapping Tables.
When this operation is executed, the complete device
configuration is saved as default configuration at which the
Save
device returns when the Reset to Default configuration is
Configuration
executed. After the device has been properly configured,
as Default
the user can decide to save it as a default configuration in
order to recover it if necessary
The P-dP Sensor calibration/trimming is saved as
Factory Calibration. This operation is typically executed
Save
in the Factory after the Sensor has been calibrated to
P-dP Sensor
the customer's specified measuring range or, in case the
as Factory
customer didn't requested any measuring range, at the
Calibration
maximum sensor range
Save Static
P Sensor as
The Static P Sensor calibration/trimming is saved as
Factory Calibration.
Factory
Calibration
Save Sensor
Temp as
The Sensor Temp. calibration/trimming is saved as
Factory
Factory Calibration
Calibration
The P-dP Sensor calibration/trimming is saved as User
Save as User
Calibration. This operation is typically executed by the
P-dP Sensor
user after the Sensor has been calibrated at the desired
Trimming
measuring range.
Save as
The Static P Sensor calibration/trimming is saved as User
User Static
Calibration
P Sensor
Trimming
Save as User
The Sensor Temp. calibration/trimming is saved as User
Sensor Temp
Calibration
Trimming

12.6 Reset

The transmitter offers some reset operations executed by
writing the proper code in the PB_FACTORY_RESET, for
details refer to the APPENDIX A - Device Mapping Tables
When this operation is executed, the complete
Reset to Default
device configuration returns to the configuration
Values
previously saved as default configuration.
This operation executes a S software restart
Warm Start-up
Reset only the Device Address to the default
Reset Bus address
address (126)
to default (126)
Return the P-dP Sensor calibration/trimming at the
calibration previously saved as Factory Calibration
Reset P-dP
This operation can be executed also with the
Sensor to Factory
optional keypad from the menu "Calibration/
Calibration
Reset/Factory Sens Trimming"
Return the Static Pressure Sensor calibration/
Reset Static P
trimming at the calibration previously saved as
Sensor to Factory
Factory Calibration
Calibration
Return the Sensor temperature calibration/
Reset Sensor
trimming at the calibration previously saved as
Temp to Factory
Factory Calibration
Calibration
Return the P-dP Sensor calibration/trimming at the
calibration previously saved as User Calibration.
Reset to User P-dP
This operation can be executed also with the
Sensor Trimming
optional keypad from the menu "Calibration/
Reset/User Sens Trimming"
Return the Static Pressure Sensor calibration/
Reset to User
trimming at the calibration previously saved as
Static P Sensor
User Calibration
Trimming
Return the Sensor temperature calibration/
Reset to User
trimming at the calibration previously saved as
Sensor Temp
User Calibration
Trimming
2600T Series Pressure transmitters | OI/266/PB-EN Rev. E 45