Appendix C - Hmi Structure - ABB 2600T Series Operating Instructions Manual

266 with profibus pa communication pressure transmitters
Hide thumbs Also See for 2600T Series:
Table of Contents

Advertisement

Appendix C – HMI structure
The HMI menu is divided in the following sections which can be selected by scrolling them acting on the buttons "2" (up) and "3"
(down) buttons, once on the display the desired sub-menu icon will be visualized, confirm your selection with the [SELECT]
BUTTON "4" (right). Follow the instruction on the screen to perform the configuration of the different parameters.
72 OI/266/PB-EN Rev. E | 2600T Series Pressure transmitters
This menu allows the verification and the parameterization of the basic configuration
of the 266 pressure transmitter. The menu driven structure will guide you to the
choice of the interface language, the tag number configuration, the engineering units,
the URV and LRV (Upper range value and lower range value), the transfer function
(linear or square root) the damping time, the auto set zero (set the input measured
value to 4 mA and the PV value to 0), the display visualization mode (the value that
need to be visualized on the LCD).
This menu allows the verification and the parameterization of the entire device The
menu driven structure includes the write protection enabling, process variable
settings (unit, LRV and URV), transfer function selection (linearization type and low
flow cut-off) and output scaling (unit according to the measurement and LRV/URV).
The last selectable sub-menu allows user to reset all the parameters to the default
configuration.
This menu allows the set-up of different functions relevant to the display itself. The
menu driven structure will guide you through the choice of some functional aspects
as the display language and contrast. Moreover, it is possible to choose in details
what you want to see on the display: one or two lines with or without bargraph.
Inside this menu there is the possibility of setting a protection password (security) and
the display scaling (linearization type, unit, LRV, URV). Display revision number
available.
This menu allows the local calibration of the instrument. The menu driven structure
will guide you through the choice of pressure sensor trimming (low or high) and at the
end you can reset these parameters (to factory sensor trimming, to user sensor
trimming).
This menu allows you to monitor diagnostics messages related to pressure variable,
output percentage, scaled output, static and sensor pressure. The menu driven
structure will also guide you through the simulation.
This menu gives you all information about the device. The menu driven structure will
show you what is the sensor type, the hardware and software revisions, the high and
low sensor limits as well as the minimum applicable span.
The last section of this structured and driven menu gives you the possibility of
changing the Tag, the Address and the Ident Number of the device.
Appendix C – HMI structure