Transponder
MDS D528
Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is
1)
adequate clearance to the metal.
Values of > 100 % related to non metal surroundings can occur if transponders were developed
2)
specifically for mounting in/on metallic surroundings.
4.3.4.5

RF260R

The RF260R can be flush-mounted in metal. Please allow for a possible reduction in the field
data values.
Figure 4-13
To avoid any impact on the field data, the distance a should be ≥ 20 mm.
Table 4- 24
Transponder
MDS D100
MDS D124
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
without metal
on metal, distance 0 mm
metal-free space for RF260R
Reduction of field data due to metal, range as %: Transponder and RF260R
without metal
1)
on metal, distance 20 mm
flush-mounted in metal;
distance all round 20 mm
without metal
1)
on metal, distance 15 mm
flush-mounted in metal;
distance all round 25 mm
RF250R with ANT 30
antenna without met-
al
100
100
Reader with-
Reader on met-
out direct
al
metal influ-
(metal plate)
ence
100
85
70
65
65
50
100
93
95
85
78
75
RF200 system planning
4.3 Installation guidelines
antenna flush-
mounted in metal
(all round 20 mm)
90
90
Reader flush-
mounted in metal
(all round 20 mm)
65
50
40
75
70
65
65