Section 4
Setting up a project
4.4
56
GUID-FEFED558-831D-4882-B4B0-9596B3535B16 V1 EN
Figure 32:
Importing IED configuration
2.
In the Import dialog box, select the .pcmi file to be imported and click Open.
After importing, the IED object is created in the plant structure.
After the .pcmi file has been imported, the IP address, the name and the technical key
of the physical IED have to be changed.

Setting IED's IP address in a project

The IP address and subnet mask of the IED object in PCM600 must match the HMI
and LAN ports of the protection relay (physical IED) to which the PC is connected.
The IP address of the protection relay can only be set via the LHMI or Parameter
Setting in PCM600. The PC and protection relay need to be on the same subnet.
There are two ways to set the IP address of an IED object in PCM600: on the first page
of the wizard when including a new IED into a project or in the IP address box of the
IED's Object Properties pane.
1MRS759117 A
REX640
Engineering Manual