Inserting An Ied In Online Mode - ABB RELION REX640 Engineering Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Setting up a project
4.3.1
44
PCM600 uses two kinds of IED files: .pcmt and .pcmi. Both files
include the complete IED configuration but their usage differs.
The .pcmt files are always accessed through the PCM600 template
manager while the .pcmi files are meant for sharing the IED instances
between different PCM600 users enabling quick import and export
from the plant structure context menu.

Inserting an IED in online mode

To set up an IED online, the protection relay must be connected to PCM600.
When the protection relay is connected to PCM600, PCM600 can read the
composition code directly from the relay. It is possible to read the full configuration
from the relay by using the Read from IED function.
1.
In the Plant Structure view, right-click the bay, point to New, point to the relay
application area such as Multiapplication IEDs and select the protection relay
type to be inserted.
Alternatively, drag an IED from the Object Types view to the
bay level.
GUID-8253DD31-085F-4C11-A623-95FCE784B706 V1 EN
Figure 20:
Selecting the protection relay type
2.
On the Configuration mode selection page, select Online Configuration and
click Next.
1MRS759117 A
REX640
Engineering Manual