Selecting the IED blocked or IED test and blocked mode

The IED blocked mode and the IED test and blocked mode can be activated by from the
IED test view. The test mode can be used for simulated testing of functions and outputs
without providing current inputs. The IED blocked mode can be used to block the physical
outputs to the process.
1.
2.
3.
4.
26
Select IED test from the main menu structure to activate the IED test view.
Figure 5. IED test view
Enable parameter editing by selecting Enable Write
Select the internal fault test by changing the New Value field selection.
Select Write to IED
The internal fault test is now activated.
Select IED test from the main menu structure to activate the IED test view.
Figure 6. IED test view
Enable parameter editing by selecting Enable Write
Select the IED blocked mode and the IED test and blocked mode by changing the
New Value field selection.
Select Write to IED
The selected test mode is now activated.
Note: If the IED blocked or IED test and blocked mode is not cancelled, it
remains on and the Start and/or Ready LEDs remain flashing.
to save changes into the IED's memory.