Commissioning

3
Commissioning
3.1

Commissioning checklist

Familiarize yourself with the IED and its functionality before you start the commissioning
work.
Ensure that you have all the needed station drawings.
Ensure that your version of the technical manual applies to the IED version you test.
Ensure that your setting software and connectivity packages work with the IED version
you test.
Find out if you need any additional software.
Ensure that you have the IED settings either on paper or in electronic format. The
settings and logic should be well documented.
Inspect the settings to ensure that they are correct.
Ensure that you have the correct cable to connect your PC to the IED's
communication port. The RJ-45 port supports any CAT 5ETHERNET cable but the
recommendation is STP.
Test your PC's communication port before you go to the site.
Find out who to contact if you have trouble and make sure you have a means to
contact them.
Find out who is responsible for the settings.
Ensure that you have with you the proper test equipment and all needed connection
cables.
Ensure that the owner of the switchgear familiarizes you with the work site and any
special aspects of it.
Ensure that you know how to operate in emergency situations. Find out where the first
aid and safety materials and exit routes are.
3.2

Checking the installation

3.2.1

Checking of the power supply

Check that the auxiliary supply voltage remains within the permissible input voltage range
under all operating conditions. Check that the polarity is correct before powering the IED.
3.3

Authorizations

3.3.1

User authorization

The user categories have been predefined for WHMI, each with different rights and
default passwords. For all user categories there are two different passwords, which are
needed for different purposes. For local connection there is a separate 'WHMI local