Troubleshooting
5.4.2
Restoring factory settings
In case of configuration data loss or any other file system error that prevents the IED from
working properly, the whole file system can be restored to the original factory state. All
default settings and configuration files stored in the factory are restored.
1.
2.
3.
4.
Results
The IED restores the factory settings and restarts. Restoring takes 1...3 minutes.
Confirmation of restoring the factory settings is shown on the display a few seconds, after
which the IED restarts.
5.4.3

Setting passwords

If user authorization is off or the user is logged in as an administrator, user passwords
can be set via the WHMI or with PCM600.
56
Note: Only the administrator can restore the factory settings.
Select Configuration > General from the main menu structure.
Enable parameter editing by selecting Enable Write
Restore the factory settings by changing the New Value field from Cancel into
Activate.
Select Write to IED
The file system is now restored to the original factory state.
Note: Avoid the unnecessary restoring of factory settings, because all the
parameter settings that are written earlier to the IED will be overwritten with
the default values. During normal use, a sudden change of the settings can
cause a protection function to trip.
to save changes into the IED's memory.
1MRS758850
.
SSC600
Operation Manual