Correction Procedures; Rebooting The Software; Restoring Factory Settings - ABB ABILITY SSC600 Operation Manual

Smart substation control and protection for electrical systems
Hide thumbs Also See for ABILITY SSC600:
Table of Contents

Advertisement

1MRS758850
Warning indication
Warning AFL error
Warning
SMV config error
Warning
Real-time task's latency excee-
ded
Warning
Redundant PSU fail
5.4

Correction procedures

5.4.1

Rebooting the software

In case of configuration data loss or any other file system error that prevents the IED from
working properly, the software can be rebooted. All default settings and configuration files
stored in the factory are restored.
1.
2.
3.
4.
SSC600
Operation Manual
Note: Only the administrator can reboot the software.
Select Configuration > General from the main menu structure.
Enable parameter editing by selecting Enable Write
Reboot the software by changing the New Value field from Cancel into Activate.
Select Write to IED
The software is now rebooted.
Warning code
33
34
117
118
to save changes into the IED's memory.
Troubleshooting
Additional information
Analog channel configuration
error.
Error in the SMV configuration.
Real-time task execution is de-
layed.
One of the power supply is faul-
ty, maintenance recommended.
.
55