IED operation
4.1.6

Committing settings

Editable values are stored either in RAM or a nonvolatile flash memory. Values stored in
the flash memory are in effect also after a reboot.
Some parameters have an edit-copy. If editing is cancelled, the values with an edit-copy
are immediately restored to the original value. The values without an edit-copy, such as
string values, are restored to the original value only after a reboot even though the edited
value is not stored in the flash memory.
1.
2.
4.1.7

Clearing and acknowledging

Reset, acknowledge or clear all messages and indications, including LEDs and latched
outputs as well as registers and recordings, in the Clear menu.
36
Click Write to IED
into IED's database for use.
The values are not stored to the flash memory.
Click Commit
Click Reject
-
If the parameter has an edit-copy, the original parameter value is restored.
-
If the parameter does not have an edit-copy, the edited parameter value
remains visible until the IED is rebooted. However, the edited value is not
stored in the nonvolatile memory and thus the reboot restores the original
value.
Figure 15. Committing changes
Note: Committing values takes a few seconds.
Note: If the values are not committed, they are not taken into use and they are
lost after a reboot.
after editing parameter values to put the values
to write the values to the flash memory.
to cancel saving settings.