Section 5 Protection And Control Engineering; Application Configuration - ABB RELION REX640 Engineering Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759117 A
Section 5
5.1
REX640
Engineering Manual
Protection and control engineering

Application Configuration

Application Configuration is used to modify an application configuration for a
protection relay and is based on IEC 61131-3 Function Block Diagrams.
The function blocks are dedicated to different functions.
Control-related functions
Protection-related functions
Monitoring functions
Communication
For more information on the function blocks, see the technical manual.
Most function blocks are mapped as logical nodes according to the IEC 61850
standard. See the IEC 61850 parameter list for more information.
If a function block is removed with Application Configuration, the
function-related data disappears from the menus as well as from the
IEC 61850 data model, with the exception of some basic function
blocks, which are mandatory and thus cannot be removed from the
relay configuration by removing them from Application
Configuration.
Other function blocks are not mapped as logical nodes; for example, logical gates.
The basic features of Application Configuration include the ability to organize a
configuration into several MainApplications as well as providing different
application programming features.
Organizing an application configuration
Organizing an application configuration into a number of logical parts
(MainApplication)
Organizing a MainApplication over a number of pages
Features for programming an application configuration
Inserting function blocks, making connections and creating variables
Including the hardware I/O channels directly in the application
configuration
Calculating the execution order automatically by clicking Calculate
execution order on the toolbar
Protection and control engineering
Section 5
65