4.8 Downloading a Program to the Inverter

After the program has been compiled normally, download it from the personal computer to the inverter.
Downloading is enabled only when the program run signal terminal (FW terminal) of the inverter is off or
the inverter is in program-stopped status. You cannot download the program in any other status.
(1) Select "Download" from the "Run" menu on the menu bar.
(You can also execute the "Download" command by clicking the
pressing the "Ctrl + F11" keys on the keyboard.)
(2) The "Program Download" dialog box appears.
(3) Click the [OK] button to start downloading.
(4) For downloading, EzSQ transfers the program from the personal computer to the memory buffer of
the inverter. The program is not stored in internal memory (EEPROM) of the inverter. After the
transfer ends, a dialog box appears to ask you whether to save the downloaded program in
EEPROM.
Click the [Yes] button to save the downloaded program in the inverter's EEPROM. Click the [No]
button to omit saving.
(5) After the download process ends, an end message dialog box appears. Click the [OK] button.
Note: If you do not save the downloaded program in the inverter's EEPROM, the downloaded program
will be deleted from the inverter when the inverter power is reset. Therefore, be sure to save the
downloaded program in the inverter's EEPROM. Even if you do not save the downloaded program
immediately after transferring it to the inverter, you can save it later by using the save operation
described below.